TM 9-2920-225-34
d. Cleaning.
There are no special cleaning procedures needed. Refer to
cleaning procedures given in para 13.
e. Inspection and Repair.
NOTE
Readings must be within limits given in table 2-5. If
readings are not within given limits, generator is non-
repairable.
1.
Check that end housing (1) and bearing retainers (2 and 3) have no cracks
or breaks. If parts are damaged, generator is nonrepairable.
Measure end housing bearing bore (4).
2.
Check that screws (5) are not bent or broken and that they have no stripped
3.
threads or damaged heads. If screws are damaged, get new ones.
Measure bearing (6) inside diameter (7) and outside diameter (8). If inside
4.
and outside diameters are not within limits given in table 2-5, get new
bearing.
Check that bearing (6) is not damaged. Refer to TM 9-214.
5.
GO
TO FRAME 2
Table 2-5. End Housing Assembly Wear Limits
Size and Fit
Wear Limits
of New Parts
Index
(inches)
(inches)
Item /Point of Measurement
Number
None
1.8497 to 1.8501
4
Inside diameter of end housing
bearing bore
None
0.7870 to 0.7874
Inside diameter of end housing
7
bearing
None
1.8499 to 1.8504
Outside diameter of end housing
8
bearing
2-161