CONTINUITY TEST
(1) Remove power distribution panel (PDP)
cover (para 16-2).
(2) Remove circuit breaker CB50 from power
distribution panel (PDP).
(3) Set multimeter to ohms.
(4) Connect positive (+) probe of multimeter
to terminal block TBC(1).
(5) Connect negative (-) probe of multimeter to
to terminal block TBC(2) and note reading
on multimeter.
(6) Connect positive (+) probe of multimeter
to terminal block TBC(2).
(7) Connect negative (-) probe of multimeter to
to terminal block TBC(3) and note reading
on multimeter.
(8) Connect positive (+) probe of multimeter
to terminal block TBC(3).
(9) Connect negative (-) probe of multimeter to
to terminal block TBC(4) and note reading
on multimeter.
(10) Connect positive (+) probe of multimeter
to terminal block TBC(4).
(11) Connect negative (-) probe of multimeter to
to terminal block TBC(5) and note reading
on multimeter.
(12) If continuity is not present between two
terminal blocks noted above, replace
jumper wire between terminal blocks that
continuity is not present (para 7-33).