TM 5-5420-279-23
NOTE
Setting the pressure transducer should only be carried out when a new pressure
transducer is being fitted to the crane. The pressure transducer can be set by pressing the
following buttons.
(7)
Press Mode/Enter and Set. After 10 seconds the LED display will go out and a new setting
can be input.
(8)
Press Mode until SP2 is displayed.
(9)
Press Set until the desired pressure is displayed 276 bar.
(10)
Press Mode until rP2 is displayed.
(11)
Press Set until the desired pressure is displayed 264 bar.
(12)
Press Mode until SP1 is displayed.
(13)
Press Set until the desired pressure is displayed 252 bar.
(14)
Press Mode until rP1 is displayed.
(15)
Press Set until the desired pressure is displayed 240 bar.
(16)
Press Mode until dr2 is displayed.
(17)
Press Set until 1 second is displayed.
(18)
Press Mode until OU1 is displayed.
(19)
Press Set until Hno is displayed.
(20)
Press Mode until OU2 is displayed.
(21)
Press Set until Hno is displayed.
(22)
Settings are not required for modes dS1, dr1 and dAP.
(23)
Lock the system by pressing Mode/Enter and Set for approximately 10 seconds. The
display will go out briefly.
(24)
Unload the crane.
(25)
Check the normal operation of the crane in accordance with the operator's manual TM 5-
5420-279-10.