CONTINUITY TEST
(1)
Disconnect swing CW solenoid connector
from swing CW solenoid.
(2)
Set multimeter to ohms.
(3)
Connect positive (+) probe of multimeter on pin
2 of swing CW solenoid cable connector.
(4)
Connect negative (-) probe of multimeter on
ground and note reading on multimeter.
(5)
Connect positive (+) probe of multimeter on pin
1 of swing CW solenoid cable connector.
(6)
Connect negative (-) probe of multimeter on
terminal board lower position 18 and note
reading on multimeter.
(7)
If continuity is not present, replace swing
CW solenoid cable (para 7-99).
(8)
If continuity is present, notify DS Maintenance.
(9)
Connect swing CW solenoid cable connector
to swing CW solenoid.
(10)
Close cover on junction box.
(11)
Tighten four screws on junction box cover.
(12)
Stow crane (TM 9-2320-366-10-1).